Hitachi SJ700-2 Series User Manual
Page 12

1 - 8
Default
Code
Function name
Monitored data or setting
_FF _FEF
_FUF
Note
b034
Run/power-on warning time
0. to 9999. (0 to 99990), 1000 to 6553 (10000 to 655300) (hr)
0.
b035 Rotational
direction
restriction
00 (enabling both forward and reverse rotations), 01 (enabling only
forward rotation), 02 (enabling only reverse rotation)
00
b036
Reduced voltage start selection
0 (minimum reduced voltage start time) to 255 (maximum reduced voltage
start time)
6
b037
Function code display restriction
00 (full display), 01 (function-specific display), 02 (user setting), 03 (data
comparison display), 04 (basic display)
04
b038 Initial-screen
selection
00 (screen displayed when the STR key was pressed last), 01 (d001), 02
(d002), 03 (d003), 04 (d007), 05 (F001)
01
Oth
er
s
b039
Automatic user-parameter
setting function enable
00 (disabling), 01 (enabling)
00
b040
Torque limit selection
00 (quadrant-specific setting), 01 (switching by terminal), 02 (analog
input), 03 (option 1), 04 (option 2)
00
b041
Torque limit (1) (forward-driving
in 4-quadrant mode)
0. to 200. (%), no (disabling torque limitation)
150.
b042
Torque limit (2)
(reverse-regenerating in
4-quadrant mode)
0. to 200. (%), no (disabling torque limitation)
150.
b043
Torque limit (3) (reverse-driving
in 4-quadrant mode)
0. to 200. (%), no (disabling torque limitation)
150.
b044
Torque limit (4)
(forward-regenerating in
4-quadrant mode)
0. to 200. (%), no (disabling torque limitation)
150.
b045
Torque limit LADSTOP enable
00 (disabling), 01 (enabling)
00
To
rque lim
itat
ion
b046
Reverse Run protection enable
00 (disabling), 01 (enabling)
00
b050
Controller deceleration and stop
on power loss
00 (disabling), 01 (nonstop deceleration to stop), 02 (DC voltage constant
control, with resume), 03 ( without resume)
00
b051
DC bus voltage trigger level
during power loss
0.0 to 999.9, 1000. (V)
220/440
b052
Over-voltage threshold during
power loss
0.0 to 999.9, 1000. (V)
360/720
b053
Deceleration time setting during
power loss
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
1.00
b054
Initial output frequency decrease
during power loss
0.00 to 10.00 (Hz)
0.00
b055
Proportional gain setting for
nonstop operation at power loss
0.00 to 2.55
0.20
Non-
st
op
oper
at
ion at
m
om
en
tar
y power
fa
ilur
e
b056
Integral time setting for nonstop
operation at power loss
0.000 to 9.999 /10.00 to 65.53 (s)
0.100
b060
Maximum-limit level of window
comparators O
0. to 100. (lower limit : b061 + b062 / 2) (%)
100
b061
Minimum-limit level of window
comparators O
0. to 100. (lower limit : b060 - b062 / 2) (%)
0
b062
Hysteresis width of window
comparators O
0. to 10. (lower limit : b061 - b062 / 2) (%)
0
b063
Maximum-limit level of window
comparators OI
0. to 100. (lower limit : b064 + b066 / 2) (%)
100
b064
Minimum-limit level of window
comparators OI
0. to 100. (lower limit : b063 - b066 / 2) (%)
0
b065
Hysteresis width of window
comparators OI
0. to 10. (lower limit : b063 - b064 / 2) (%)
0
b066
Maximum-limit level of window
comparators OI
-100. to 100. (lower limit : b067 + b068 / 2) (%)
100
b067
Minimum-limit level of window
comparators O/OI/O2
-100. to 100. (lower limit : b066 - b068 / 2) (%)
0
b068
Hysteresis width of window
comparators O/OI/O2
0. to 10. (lower limit : b066 - b067 / 2) (%)
0
b070
Operation level at O
disconnection
0. to 100. (%) or "no" (ignore)
no
b071
Operation level at OI
disconnection
0. to 100. (%) or "no" (ignore)
no
Window com
par
at
or
b072
Operation level at O2
disconnection
-100. to 100. (%) or "no" (ignore)
no