Hitachi SJ700-2 Series User Manual
Page 16

1 - 12
Default
Code
Function name
Monitored data or setting
_FF _FEF _FUF
Note
C038
Low-current indication signal
output mode selection
00 (output during acceleration/deceleration and constant-speed operation),
01 (output only during constant-speed operation)
01
C039
Low-current indication signal
detection level
0.0 to 2.00 x "rated current" (A)
Rated current of
inverter
C040
Overload signal output mode
00 (output during acceleration/deceleration and constant-speed operation),
01 (output only during constant-speed operation)
01
C041
Overload level setting
0.0 to 2.00 x "rated current" (A)
Rated current of
inverter
C042
Frequency arrival setting for accel. 0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
C043
Frequency arrival setting for decel. 0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
C044
PID deviation level setting
0.0 to 100.0 (%)
3.0
C045
Frequency arrival setting for
acceleration (2)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
C046
Frequency arrival setting for
deceleration (2)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
C052
Maximum PID feedback data
0.0 to 100.0 (%)
100.0
C053
Minimum PID feedback data
0.0 to 100.0 (%)
0.0
C055
Over-torque (forward-driving) level
setting
0. to 200. (%)
100.
C056
Over-torque (reverse
regenerating) level setting
0. to 200. (%)
100.
C057
Over-torque (reverse driving) level
setting
0. to 200. (%)
100.
C058
Over-torque (forward
regenerating) level setting
0. to 200. (%)
100.
C061
Electronic thermal warning level
setting
0. to 100. (%)
80.
C062
Alarm code output
00 (disabling), 01 (3 bits), 02 (4 bits)
00
C063
Zero speed detection level
0.00 to 99.99, 100.0 (Hz)
0.00
Levels and ou
tput t
er
m
inal sta
tus
C064
Heat sink overheat warning level
0. to 200.0 (
°C)
120.
C071
Communication speed selection
02 (loopback test), 03 (2,400 bps), 04 (4,800 bps), 05 (9,600 bps), 06
(19,200 bps)
04
C072
Node allocation
1. to 32.
1.
C073
Communication data length
selection
7 (7 bits), 8 (8 bits)
7
C074
Communication parity selection
00 (no parity), 01 (even parity), 02 (odd parity)
00
C075
Communication stop bit selection
1 (1 bit), 2 (2 bits)
1
C076
Selection of the operation after
communication error
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02
(ignoring errors), 03 (stopping the motor after free-running), 04
(decelerating and stopping the motor)
02
C077
Communication timeout limit
before tripping
0.00 to 99.99 (s)
0.00
C078
Communication wait time
0. to 1000. (ms)
0.
Com
m
unica
tion f
unc
tion
C079
Communication mode selection
00(ASCII), 01(Modbus-RTU)
00
C081
[O] input span calibration
0. to 9999., 1000 to 6553(10000 to 65530)
Factory setting
C082
[OI] input span calibration
0. to 9999., 1000 to 6553(10000 to 65530)
Factory setting
C083
[O2] input span calibration
0. to 9999., 1000 to 6553(10000 to 65530)
Factory setting
C085
Thermistor input tuning
0.0 to 999.9, 1000.
Factory setting
Adjust
m
ent
C091
Debug mode enable
(Do not change this parameter, which is intended for factory adjustment.)
00
C101
Up/Down memory mode selection 00 (not storing the frequency data), 01 (storing the frequency data)
00
C102 Reset
mode
selection
00 (resetting the trip when RS is on), 01 (resetting the trip when RS is off), 2
(enabling resetting only upon tripping [resetting when RS is on])
00
Oth
er
s
C103
Restart mode after reset
00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (restarting
with active matching frequency),03(resetting only trip)
00
C105
FM gain adjustment
50. to 200. (%)
100.
C106
AM gain adjustment
50. to 200. (%)
100.
C107
AMI gain adjustment
50. to 200. (%)
100.
C109
AM bias adjustment
0. to 100. (%)
0.
Me
te
r
adjust
m
en
t
C110
AMI bias adjustment
0. to 100. (%)
20.