Hitachi SJ700-2 Series User Manual
Page 18

1 - 14
Default
Code
Function name
Monitored data or setting
_FF _FEF
_FUF
Note
H001 Auto-tuning
Setting
00 (disabling auto-tuning), 01 (auto-tuning without rotation), 02 (auto-tuning
with rotation)
00
H002
Motor data selection, 1st motor
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
00
H202
Motor data selection, 2nd motor
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
00
H003
Motor capacity, 1st motor
0.20 to 75.00 (kW)
Factory setting
H203
Motor capacity, 2nd motor
0.20 to 75.00 (kW)
Factory setting
H004
Motor poles setting, 1st motor
2, 4, 6, 8, 10 (poles)
4
H204
Motor poles setting, 2nd motor
2, 4, 6, 8, 10 (poles)
4
H005
Motor speed constant, 1st motor
0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000)
1.590
H205
Motor speed constant, 2nd motor
0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000)
1.590
H006
Motor stabilization constant, 1st
motor
0. to 255.
100.
H206
Motor stabilization constant, 2nd
motor
0. to 255.
100.
H306
Motor stabilization constant, 3rd
motor
0. to 255.
100.
H020
Motor constant R1, 1st motor
0.001 to 9.999, 10.00 to 65.53 (
Ω)
Depending on motor capacity
H220
Motor constant R1, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (
Ω)
Depending on motor capacity
H221
Motor constant R2, 1st motor
0.001 to 9.999, 10.00 to 65.53 (
Ω)
Depending on motor capacity
H221
Motor constant R2, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (
Ω)
Depending on motor capacity
H222
Motor constant L, 1st motor
0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on motor capacity
H222
Motor constant L, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on motor capacity
H223
Motor constant Io
0.01 to 99.99, 100.0 to 655.3 (A)
Depending on motor capacity
H223
Motor constant Io, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (A)
Depending on motor capacity
H224
Motor constant J
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
Depending on motor capacity
H224
Motor constant J, 2nd motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
Depending on motor capacity
H030
Auto constant R1, 1st motor
0.001 to 9.999, 10.00 to 65.53 (
Ω)
Depending on motor capacity
H230
Auto constant R1, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (
Ω)
Depending on motor capacity
H231
Auto constant R2, 1st motor
0.001 to 9.999, 10.00 to 65.53 (
Ω)
Depending on motor capacity
H231
Auto constant R2, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (
Ω)
Depending on motor capacity
H232
Auto constant L, 1st motor
0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on motor capacity
H232
Auto constant L, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on motor capacity
H233
Auto constant Io, 1st motor
0.01 to 99.99, 100.0 to 655.3 (A)
Depending on motor capacity
H233
Auto constant Io, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (A)
Depending on motor capacity
H234
Auto constant J, 1st motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
Depending on motor capacity
Cont
ro
l cons
tan
ts
H234
Auto constant J, 2nd motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
Depending on motor capacity