Raised hearth extension framing, Flush hearth extension framing – Hearth and Home Technologies BIR50-B User Manual

Page 40

background image

40

IMPORTANT! Hearth extension design must be determined

before installation of fireplace.

Floor

Non-combustible

Framing Material

Non-combustible

Finishing Material

Protective Metal

Hearth Strips

1 in. Micore or

equivalent insulation

& 1/2 in. Durock

Note: The bottom of the

fireplace opening is 3-3/4 in.

(95.3mm) above the bottom

of the fireplace. Finished

hearth extension must NOT

extend above this level.

Platform must be built

to raise the bottom of

the fireplace opening

to the level of the

desired hearth height.

20 in. Min.

Hearth Extension

Figure 12.3 Raised Platform Hearth Extension Detail

Raised Hearth Extension Framing

The hearth framing must be constructed of non-combus-

tible materials (Figure 12.2) and placed on 1/2 in. Durock

and 1 in. Micore (or equivalent material) (Figure 12.4).

When creating the platform, allow for the thickness of the

non-combustible finishing materials (Figure 12.5).

* 2 in. (51 mm)

Continuous,

non-combustible sealant

Tile, stone or other

non-combustible material

Floor constructed of wood or

other combustible material

1 in. Micore or

equivalent

insulation

(see Table)

Fireplace

Protective

Metal Hearth

Strip

1/2 in. Durock

*

*

Note: The bottom of the fireplace opening

is 3-3/4 in. (95.3mm) above the bottom of

the fireplace. Finished hearth extension

must NOT extend above this level.

Figure 12.2 Standard Hearth Extension Construction

Flush Hearth Extension Framing

• If the hearth extension and fireplace are recessed into

a combustible floor, the hearth extension must extend a

minimum of 30 inches in front of the unit.

• The fireplace should not be recessed more than 3 3/4 in.

(95.3 mm) below the surface of the finished floor.

• Refer to Figure 12.4.

Figure 12.4 Flush Hearth Extension Side View

Non-combustible Finishing Material

Protective Metal

Hearth Strip

30 in. Min.

Hearth Extension

1 in. (25.4 mm)

Micore and

1/2 in. (13 mm)

Durock

Finished

Floor

Bottom of

Fireplace Opening

Note: The bottom of the fireplace opening

is 3-3/4 in. (95.3mm) above the bottom of

the fireplace. Finished hearth must NOT

extend above this level.

Heatilator • Birmingham BIR50-B • 4059-682D • 9/12