K. Install Attic Insulation Shield

The attic insulation shield must be installed where the

chimney passes into an attic. Its purpose is to prevent

debris and insulation from getting too close to the chimney.

In attic areas where this shield cannot fit, or is not used you

must enclose the attic portion of the chimney in a framed

enclosure. If the chimney is fully enclosed through the attic,

an attic insulation shield is not required. Install the attic

insulation shield as follows:
• Remove any insulation from attic floor around the framed

opening.

• Assemble chimney sections until at least 18 inches of

chimney extends above the firestop.

• Slip the attic insulation shield over the chimney until the

base sits squarely on the framed opening (Figure 8.10).

• Secure the attic insulation shield to the top of the framed

opening using at least two 8-penny nails ort wo #8,

1-1/2 in. wood screws per side (Figure 8.11).

• Wrap the collar of the attic insulation shield around the

chimney and fasten it loosely. Slide the collar down to meet

the attic insulation shield. Tighten the bolts to secure the

collar in place (Figure 8.11).

Attic

Insulation

Shield

Firestop

Attic

Figure 8.10

Attic

Attic Shield

Collar

Firestop

Figure 8.11

L. Install Roof Radiation Shields

Roof radiation shields must be used to provide protection

for roof or chase framing members.
Note: Roof radiation shields do not allow for a reduced

clearance to combustibles.
Clearance to combustibles must be a minimum of 2” away

from the chimney pipe.
• Install roof radiation shields at either the top of the chase

or where the chimney penetrates the roof, whichever is

the top of the installation.

• Roof radiation shields are built with a 1/2” air gap standoff

from the joist face (Figure 8.12). The corners of the roof

radiation shields overlap each other to ensure proper

position.

• Secure the roof radiation shields to the top of the framing

members using screws or nails in the corners.

• If framing members are further away from the chimney

than 2 in., center the roof radiation shield to the chimney

on the framing member and secure in place with screws

or nails.

(4) Roof

Radiation

Shields

Chase

Enclosure

Figure 8.12

M. Attach Flashing

For chase enclosures, use the Chase Top Flashing. The

Chase Top Flashing allows for a 1-1/2 in. clearance main-

tained from the chimney (Figure 8.14) and provides re-

quired ventilation air.
• Chase Top Flashings (includes Chase Top Collars and

Spacing Clips) are available from your HHT dealer.

• Additional non-combustible structural supports can be

field-fabricated to help support the Chase Top Flashing

if needed, provided the air ventilation requirements are

maintained. See Figure 8.15.

• If the ChaseTop Flashing (40 in. x 40 in.) does not ensure

the minimum 1/2 in. spacing and perimeter ventilation

requirements as shown in Figure 8.13., use a Chase Top

Collar and field-construct the flashing as needed for the

chase dimensions. Skip to Field-Constructed Chase Top

Flashing.