33

Roof radiation

shields

Allow a 1 in. (25 mm) air gap between

storm collar and chase top flashing

1/2 in. (13 mm) air space

established by spacers

1/2 in.

overhang

14 in. (345 mm)

diameter chimney

must extend at least

6 in. (152 mm) above

chase top flashing.

DuraChimney II

Pipe

1/2 in.

(13 mm)

Spacers for chase

top flashing

Chase Top

Flashing

Storm Collar

20 in. diameter

opening

Chimney Cap

Maintain 2 in. (51 mm)

clearance between

DuraChimney II and

chase enclosure

• Chase top shrouds may be field constructed where

permitted by regional building codes.

WARNING! Risk of Fire! Shrouds must be constructed as

specified. Improper construction may overheat chase top.

NOTICE: Some regional codes require an agency-Listed

shroud. Consult your local building officials.

10

Shrouds

• Hearth & Home Technologies Inc. supplies UL listed

shrouds. See your dealer for details.

A. Shroud Requirements

Figure 10.1 Shroud Requirements

Shrouds can either be field-fabricated or factory-fabricated,

but they must meet the requirements as specified in these

instructions. Shrouds must be constructed of a minimum

24 ga (.024 in.) stainless steel, aluminized steel, galva-

nized steel, or copper. Other materials may also be used,

such as brick, mortar, stucco, stone, etc. provided they are

completely non-combustible. Check with your local building

code authroities for any additional shroud requirements.

Shrouds must be able to be removed to allow chimney ac-

cess to properly clean the chimney. DuraChimney II instal-

lations which include the use of a shroud must comply with

the following requirements (Figure 10.1)

• DuraChimney II must maintain at least 2 in. (51 mm)

clearance from combustible materials.

• The chase enclosure must be ventilated.

• The chase top flashing or field-fabricated chase pan must

be used. Field-fabricated chase pans are acceptable if

they meet these requirements:

- Material must be 24 ga (.024 in) galvanized steel or

equivalent.

- Chase pan must have opening 3 in. (76 mm) larger

than outside diameter of chimney pipe with at least a

1/2 in. (13 mm) upturned flange/collar.

- Chase pan must overhang chase by 1/2 in. (13 mm)

per side for proper air flow.

- Chase pan must have a 1 in. (25 mm) down turned

outside edge (weather protection).

Heatilator • Birmingham BIR50-B • 4059-682D• 9/12