beautypg.com

Hoshizaki KML "F" SERIES User Manual

Page 36

background image

36

[c] SEQUENCE

1st Cycle

1. Unit energized and Control Switch to “ICE”
position. Water supply cycle starts.

2. After 1 minute,
Defrost cycle starts.

3. Thermistor reads 48° F.
Defrost Timer starts counting.

IMPORTANT

Water Valve
opening is limited
to 6 minutes.

&

5. After the first 5 minutes in freeze cycle.
Ready to complete freeze cycle when Float
Switch circuit opens.

4. Defrost Timer stops counting.
Defrost cycle is completed and freeze cycle
starts.

IMPORTANT

Board never accepts freeze completion signal
within the first 5 minutes in freeze cycle.

IMPORTANT

1. Board never accepts defrost completion
signal within the first 2 minutes in defrost
cycle.

2. Defrost cycle time is limited to 20 minutes
even if Defrost Timer does not stop counting.

This manual is related to the following products: