beautypg.com

Hoshizaki KML "F" SERIES User Manual

Page 35

background image

35

(Control Products HOS-001A Board)

The application switch located between relay X3 & X4 must be set to match the original
board application. Place this switch in the ALP position if there is no white wire supplied
to the K1 connector. If there is a white wire, place the switch in the C position. If this
switch is placed in the wrong position, either the compressor contactor will remain ener-
gized with the control switch OFF, or the unit will not start.

The dip switches should be adjusted per the adjustment chart published in the Tech
Specs book. Number 8 must remain in the OFF position.

This manual is related to the following products: