Set Up and Calibration Procedures
Maintenance Set Up Group
60
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
Revision 7
7/08
Actuator Lower
Display
Prompt
Selections or
Range of Setting
Parameter Definition/PDA HercuLink
®
Prompt
PDA users: The prompts are organized differently on your PDA’s
HercuLink
®
software. Grayed prompts are under Configuration, Maintenance. Non-grayed
prompts are under Maintenance.
DATSAV
DIS
ENAB
MAINTENANCE DATA FORCED SAVE
— Allows you to
manually force a save of the current maintenance data
values.
DISABLE
— Forced data save is disabled.
ENABLE
— Forced data save is enabled.
PASSWRD
nnnn
PASSWORD
— If a password has been activated, then a 4-
digit password is required to enable any of the functions
below.
NOTE: Password is set (or changed) from the Lock set up
group.
MANRST
NONE
STAL
STRT
REGNn
n
= 0 to 9
TEMP
TDEG
RELn
n
= 1, 2, 3 or 4
ALL
SYST
default = NONE
MAINTENANCE STATISTIC RESET
— Allows reset of the
following maintenance statistics:
None
— No reset of maintenance statisitics
Stall
— Resets accumulated stall time to zero.
Motor Starts
— Resets the accumulated motor start counter
to zero.
Motor Starts in the Region
— Resets the selected motor
span region counter to zero.
Temperature Statistics
— Resets the high / low
temperature limit statistics.
Total Degrees
— Resets the total degrees of motor travel to
zero.
Relay Counts
— Resets the selected accumulated relay
cycle counter to zero.
All
— Resets all maintenance statistics to zero.
SYST
— Enables the system restart function.