Installation
Electrical Installation
18
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
Revision 7
7/08
HercuLine
®
2000 Terminal Connections
Table 3 Terminal Connections: HercuLine
®
2000
Connection
Terminal Numbers
and LABEL
See Figure 8
Descriptions
Hot 1
Hot wire for 120/240VAC mains supply. Use only if Auto/Manual
switch is present.
Neutral
2
Neutral wire for 120/240VAC mains supply
Auto/Manual Switch
Contact
3
4
Switch contact to indicate setting of actuator AUTO/MANUAL
switch.
Switch is closed when actuator is “NOT-IN-AUTO”
CW from Controller
5
CW motor drive
CCW from Controller
6
CCW motor drive
Potentiometer #1
7
8
9
Clockwise-End
Slider
Counterclockwise-End
Potentiometer #2
10
11
12
Clockwise-End
Slider
Counterclockwise-End
Protective Ground
Ground wire connection for mains supply
158 ohm
158 ohm
Install resistors to convert 1000 ohm
potentiometer to 135 ohms
1
1
REQUIRED ONLY IF AUTO/MANUAL
SWITCH IS PRESENT
158 ohm
158 ohm
Install resistors to convert 1000 ohm
potentiometer to 135 ohms
1
1
1
1
REQUIRED ONLY IF AUTO/MANUAL
SWITCH IS PRESENT
Figure 8 HercuLine
®
2000 connections