Honeywell HERCULINE 2000 User Manual
Page 55

Set Up and Calibration Procedures
Relays Set Up Group
Revision 7
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
47
7/08
Relay Type - Deviation
Setting up a relay to alarm (energize) when the motor position deviates 10% (+ or -) from the actuator
setpoint can be set up as follows.
Set Up Group
Parameter
Value
SET RELAY1
RTYP11
DEV
R11VAL
10.00
R11HL
HI
RTYP12
DEV
R12VAL
-10.00
R12HL
LO
RLY1HY
0.0
The resulting action is shown below.
100%
0%
Closed
-10%
RELAY n
Normally Open
Closed
Open
Motor
Position
Input
50%
+10%