beautypg.com

Power up self test diagnostics – Honeywell HERCULINE 2000 User Manual

Page 116

background image

Troubleshooting
Troubleshooting Procedures

108

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

Power Up Self Test Diagnostics

Replace display

assembly.

Cycle power to
actuator. If CALTST
fails again, replace

CPU assembly.

Cycle power to
actuator. If CFGTST
fails again, replace

CPU assembly.

Replace CPU

Assembly.

Observe self test.

Cycle power
to actuator.

Does display

light up?

RAMTST PASS?

SEETST PASS?

CALTST PASS?

Do all LEDs

and display

segments light

up?

CFGTST PASS?

Check actuator

configuration

(setup), reconfigure

if necessary.

Check actuator

calibration,

recalibrate

if necessary.

E

B

Yes

No

A

Yes

No

No

Yes

Yes

No

Yes

No

No

Yes

Figure 43 Power Up Diagnostics

Test Non-Contact Sensor PWA

See page 85.