Installer self-test, Caution – Honeywell CHRONOTHERM T8611G User Manual
Page 9
T8611G CHRONOTHERM
®
DELUXE ZONING HEAT PUMP THERMOSTAT
9
69-1414—2
INSTALLER SELF-TEST
Use the Installer Self-Test to check the thermostat
operation. Refer to Table 5 for a list of the available
self-tests.
Table 5. Tests Available In Installer Self-Test.
CAUTION
Equipment Damage Hazard.
Minimum compressor off-time is bypassed
during the Installer System Test.
Avoid cycling compress quickly.
To start the system test:
Press and hold the increase and decrease keys at
the same time until 10 appears. All segments of the
display are displayed before the 10 appears.
See Fig. 10 and 11.
Fig. 11. Display of all LCD segments.
Fig. 12. Display of test number.
Refer to Table 6 for the directions and results of the
specific tests.
NOTE: Press Time
∆ to advance to the next test and
Time
∇ to go back to the previous test. Press
Run Program to exit the system test.
Test
Number
System Test Description
10-19
Heating equipment can be turned on and off.
20-29
Emergency heat equipment can be turned
on and off.
30-39
Cooling equipment can be turned on and off.
40-49
Fan equipment can be turned on and off.
60 0 to
60 19
Keyboard keys test.
70-79
Thermostat information including date code
and software versions are displayed.
M14559
Aux Ht
Set Day/Time
Set Program
Mon
Wake Leave Return
Sleep
Outdoor
Room
Filter
Wait
System
Fan
Em Heat
On
Auto
Off
Cool
Auto
AM
PM
Hold for
Heat
Cool
Repl Batt
Recovery
DST
Tue Wed Thu Fri Sat Sun
Days
Temporary Setting
Em Ht
M14612
Table 6. Installer System Test Options.
Keys to
Press
Test
Number
Description
Heating Equipment Self-Test
Time
∆
10
Enter heating equipment self-test.
11
Stage-one heat comes on. The system fan is also energized.
12
Stage-two heat comes on. Stage-one heat and system fan remain on.
11
Stage-two heat turns off.
10
Stage-one heat and system fan turn off.
Emergency Heating Equipment Self-Test
Time
∆
20
Change from heating to emergency heating equipment self-test.
21
Emergency heat and system fan come on.
22
Stage 2 heat comes on.
21
Stage 2 heat turns off.
20
Emergency heat and system fan turn off.
Cooling Equipment Self-Test
Time
∆ 30
Change from heating or emergency heating to cooling equipment self-test.
31
Cool and system fan come on.
30
Cool and system fan turn off.
Fan Equipment Self-Test
Time
∆
40
Change from cooling to fan equipment self- test.