Honeywell CHRONOTHERM T8611G User Manual
Page 7
T8611G CHRONOTHERM
®
DELUXE ZONING HEAT PUMP THERMOSTAT
7
69-1414—2
IMPORTANT
Review the settings to confirm that they match
the system. Press Run Program to exit the
Installer Setup. The thermostat has saved the
Installer Setup changes and initiated a reset in
order to operate using the new settings. Be sure
to set the current day and time immediately.
Temperature
display
adjustment.
37
0
No difference in
displayed
temperature and
actual room
temperature.
3 thru -3
or
1.5 thru
-1.5
1 (0.5)—Display adjusts to
1°F (0.5°C) higher than
actual room temperature.
2 (1.0)—Display adjusts to
2°F (1.0°C) higher than
actual room temperature.
3 (1.5) —Display adjusts to
3°F (1.5°C) higher than
actual room temperature.
-1 (-0.5) —Display adjusts to
-1°F (-0.5°C) lower than
actual room temperature.
-2 (-1.0) —Display adjusts to
-2°F (-1.0°C) lower than
actual room temperature.
-3 (-1.5) —Display adjusts to
-3°F (-1.5°C) lower than
actual room temperature.
Furnace Air
Filter Timer.
43
2
30 days (System
run time)
0, 1, 3, 4
0 – off
1 – 10 days
3 – 60 days
4 – 120 days
(Time is counted when heat,
cool or fan is running.)
Humidifier Pad
Monitor.
44
0
Off
1, 2, 3
1 – 90 days
2 – 180 days
3 – 365 days
(Time is counted by calendar
days in heat mode.)
Ultraviolet (UV)
Air Treatment
System Lamp
Monitor.
45
0
Off
1
1 – 365 days
(Time is counted by calendar
days in any mode.)
Table 4. Thermostat Installer Setup Options. (Continued)
Select
Installer Setup
Number (Press
Time
∆ key to
change)
Factory Setting
Other Choices
(Press or key to change)
Actual
Setting
Display
Description
Display
Description