Chapter 8 list of data settings – Hitachi SJ700-2 User Manual
Page 274

Chapter 8 List of Data Settings
8 - 14
Default
Code
Function name
Monitored data or setting
_FF _FEF
_FUF
Setting
during
operation
(allowed
or not)
Change
during
operation
(allowed
or not)
Page
H050
PI proportional gain for 1st motor
0.0 to 999.9, 1000.
100.0
{
{
H250
PI proportional gain for 2nd motor
0.0 to 999.9, 1000.
100.0
{
{
H051
PI integral gain for 1st motor
0.0 to 999.9, 1000.
100.0
{
{
H251
PI integral gain for 2nd motor
0.0 to 999.9, 1000.
100.0
{
{
H052
P proportional gain setting for 1st
motor
0.01 to 10.00
1.00
{
{
H252
P proportional gain setting for 2nd
motor
0.01 to 10.00
1.00
{
{
H060
Zero LV lmit for 1st motor
0.0 to 100.0
100.0
{
{
H260
Zero LV lmit for 2nd motor
0.0 to 100.0
100.0
{
{
4-58
H061
Zero LV starting boost current for
1st motor
0. to 50. (%)
50.
{
{
H261
Zero LV starting boost current for
2nd motor
0. to 50. (%)
50.
{
{
4-90
H070
Terminal selection PI proportional
gain setting
0.0 to 999.9, 1000.
100.0
{
{
H071
Terminal selection PI integral gain
setting
0.0 to 999.9, 1000.
100.0
{
{
H072
Terminal selection P proportional
gain setting
0.00 to 10.00
1.00
{
{
Cont
ro
l cons
tan
ts
H073
Gain switching time
0. to 9999. (ms)
100.
{
{
4-58