Chapter 8 List of Data Settings
8 - 8
Default
Code
Function name
Monitored data or setting
_FF _FEF _FUF
Setting during
operation
(allowed or
not)
Change
during
operation
(allowed or
not)
Page
b078
Cumulative input power data
clearance
Clearance by setting "01" and pressing the STR key
00
{
{
b079
Cumulative input power display
gain setting
1. to 1000.
1.
{
{
4-4
b082
Start frequency adjustment
0.10 to 9.99 (Hz)
0.50
¯
{
4-42
b083
Carrier frequency setting
0.5 to 15.0 (kHz) (subject to derating)
5.0
¯
¯
4-43
b084
Initialization mode (parameters or
trip history)
00 (clearing the trip history), 01 (initializing the data),
02 (clearing the trip history and initializing the data)
00
¯
¯
b085
Country code for initialization
00 (Japan), 01 (EU), 02 (U.S.A.)
00
01
02
¯
¯
4-75
b086
Frequency scaling conversion
factor
0.1 to 99.0
1.0
{
{
4-2
b087
STOP key enable
00 (enabling), 01 (disabling), 02 (disabling only the function to stop)
00
¯
{
4-9
b088
Restart mode after FRS
00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (starting
with active matching frequency)
00
¯
{
4-52
b089
Automatic carrier frequency
reduction
00: invalid, 01: valid
00
¯
¯
4-44
b090
Dynamic braking usage ratio
0.0 to 100.0 (%)
0.0
¯
{
4-45
b091
Stop mode selection
00 (deceleration until stop), 01 (free-run stop)
00
¯
{
4-9
b092 Cooling
fan
control
00 (always operating the fan), 01 (operating the fan only during inverter
operation [including 5 minutes after power-on and power-off])
00
¯
{
b095
Dynamic braking control
00 (disabling), 01 (enabling [disabling while the motor is topped]), 02
(enabling [enabling also while the motor is topped])
00
¯
{
b096
Dynamic braking activation level
330 to 380, 660 to 760(V)
360/
720
¯
{
4-45
b098
Thermistor for thermal protection
control
00 (disabling the thermistor), 01 (enabling the thermistor with PTC), 02
(enabling the thermistor with NTC)
00
¯
{
Oth
e
rs
b099
Thermal protection level setting
0. to 9999. (
Ω)
3000.
¯
{
4-72
b100
Free-setting V/f frequency (1)
0. to "free-setting V/f frequency (2)" (Hz)
0.
¯
¯
b101
Free-setting V/f voltage (1)
0.0 to 800.0 (V)
0.0
¯
¯
b102
Free-setting V/f frequency (2)
0. to "free-setting V/f frequency (3)" (Hz)
0.
¯
¯
b103
Free-setting V/f voltage (2)
0.0 to 800.0 (V)
0.0
¯
¯
b104
Free-setting V/f frequency (3)
0. to "free-setting V/f frequency (4)" (Hz)
0.
¯
¯
b105
Free-setting V/f voltage (3)
0.0 to 800.0 (V)
0.0
¯
¯
b106
Free-setting V/f frequency (4)
0. to "free-setting V/f frequency (5)" (Hz)
0.
¯
¯
b107
Free-setting V/f voltage (4)
0.0 to 800.0 (V)
0.0
¯
¯
b108
Free-setting V/f frequency (5)
0. to "free-setting V/f frequency (6)" (Hz)
0.
¯
¯
b109
Free-setting V/f voltage (5)
0.0 to 800.0 (V)
0.0
¯
¯
b110
Free-setting V/f frequency (6)
0. to "free-setting V/f frequency (7)" (Hz)
0.
¯
¯
b111
Free-setting V/f voltage (6)
0.0 to 800.0 (V)
0.0
¯
¯
b112
Free-setting V/f frequency (7)
0. to "free-setting V/f frequency (8)" (Hz)
0.
¯
¯
F
re
e
se
tti
n
g
o
f V
/f ch
a
ra
c
te
ri
s
ti
c
b113
Free-setting V/f voltage (7)
0.0 to 800.0 (V)
0.0
¯
¯
4-17
b120
Brake Control Enable
00 (disabling), 01 (enabling)
00
¯
{
b121
Brake Wait Time for Release
0.00 to 5.00 (s)
0.00
¯
{
b122
Brake Wait Time for Acceleration
0.00 to 5.00 (s)
0.00
¯
{
b123
Brake Wait Time for Stopping
0.00 to 5.00 (s)
0.00
¯
{
b124
Brake Wait Time for Confirmation
0.00 to 5.00 (s)
0.00
¯
{
b125
Brake Release Frequency Setting 0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
b126
Brake Release Current Setting
0.0 to 2.00 x "rated current"
Rated current of inverter
¯
{
b127
Braking frequency
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
4-81
b130
Overvoltage suppression enable
00 (disabling the restraint), 01 (controlled deceleration), 02 (enabling
acceleration)
00
¯
{
b131
Overvoltage suppression level
330 to 390 (V) (200 V class model), 660 to 780 (V) (400 V class model)
380/
760
¯
{
b132
Acceleration and deceleration
rate at overvoltage suppression
0.10 to 30.00 (s)
1.00
¯
{
b133
Overvoltage suppression
propotional gain
0.00 to 2.55
0.50
{
{
Oth
e
rs
b134
Overvoltage suppression Integral
time
0.000 to 9.999 / 10.00 to 65.53 (s)
0.060
{
{
4-41