beautypg.com

Termination locations, Warning, A. vent termination minimum clearances – Hearth and Home Technologies BCBV36I User Manual

Page 20

background image

Heatilator • BCBV36 • 4008-033 • Rev F • 12/08

20

A. Vent Termination Minimum Clearances

Gas, Wood or Fuel Oil

Termination Cap

B

Gas

Termination

Cap **

A *

*

If using decorative cap cover(s), this distance may need to be
increased. Refer to the installation instructions supplied with the
decorative cap cover.

**

In a staggered installation with both gas and wood terminations, the
wood termination cap must be higher than the gas termination cap.

A

B

6 in. (minimum) up to 20 in.

152 mm/508 mm

18 in. minimum

457 mm

20 in. and over

0 in. minimum

Figure 6.1 Minimum Height From Roof To Lowest Discharge
Opening

6

6

Termination Locations

Fire Risk.
Maintain vent clearance to combustibles as
specifi ed.
DO NOT pack air space with insulation or other

materials.

Failure to keep insulation or other materials away
from vent pipe may cause overheating and fi re.

WARNING

Figure 6.2 Multiple Termination Caps

12

X

8 ft

(2.44 m)

Lowest

Discharge

Opening

Termination

Cap

Roof Pitch
is X / 12

Vertical
wall

H (min.) - Minimum height
from roof to lowest
discharge opening.

Roof Pitch

H (Min.) Ft.

Roof Pitch

H (Min.) Ft.

Flat to 6/12

1.0*

Over 11/12 to 12/12

4.0

Over 6/12 to 7/12

1.25*

Over 12/12 to 14/12

5.0

Over 7/12 to 8/12

1.5*

Over 14/12 to 16/12

6.0

Over 8/12 to 9/12

2.0*

Over 16/12 to 18/12

7.0

Over 9/12 to 10/12

2.5

Over 18/12 to 20/12

7.5

Over 10/12 to 11/12 3.25

Over 20/12 to 21/12

8.0

* 3 ft. minimum in snow regions

Storm Collar

Roof

Flashing

О