Model OFE/OFG-321,322,323,324
Ventilation must conform to local, state, and national
codes. Consult your local fire department or building
authorities.
When installing the gas open fryer, do not attach an
extension to the gas flue exhaust stack. This may impair
proper operation of the burner, causing malfunctions
and possible negative back draft.
2-6. GAS SUPPLY
The gas open fryer is factory available for either natural or propane
gas. Check the data plate inside the front door of the
cabinet to determine the proper gas supply requirements. The
minimum supply for natural gas is 7 inches water column
(1.7 kPa), and 10 inches water column (2.49 kPa) for propane.
Do not attempt to use any gas other than that specified
on the data plate. Incorrect gas supply could cause a fire
or explosion resulting in severe injuries and/or property
damage.
Please refer below for the recommended hookup of the fryer to
main
gas
line
supply.
To avoid possible serious personal injury:
•
Installation must conform with local, state, and national
codes, the American National Standard Z223.1-(the latest
edition) National Fuel Gas Code, and the local
municipal building codes. In Canada, installation must be
in accordance with Standard CAN/CSA B 149.1 &
Installation
Codes
-
Gas
Burning Appliances and local codes.
In Australia, in accordance with Australian Gas
Authority
rules
AG601-2000,
section
AS5601.