E. vent diagrams, Top vent - horizontal termination, One elbow – Hearth and Home Technologies IDV4833ILH User Manual

Page 23

background image

Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08

23

H

1

V

1

To replace the fi rst starter elbow with two 45° elbows, refer
to Figure 7.4. All other 90° elbows can be replaced with
two 45° elbows.
General Rules:
• SUBTRACT 3 ft. from the total H measurement for each

90° elbow installed horizontally.

• SUBTRACT 1-1/2 ft. from the total H measurement for

each 45° elbow installed horizontally.

• A maximum of three 90° elbows (or six 45° elbows) may

be used in any vent confi guration. Some elbows may be
installed horizontally. See Figure 7.9.

E. Vent Diagrams

Figure 7.3

One Elbow

1. Top Vent - Horizontal Termination

V

1

min.

V

1

max.

H

1

max.

ft

m

ft

m

ft

m

1

0.30

-

-

25 in. 635 mm

1.5

0.46

-

-

18

5.49

2

0.61

-

-

25

7.62

-

-

25

7.62

25

7.62

• Elbows may be placed back to back anywhere in the

system as long as the fi rst 90° elbow is a starter elbow
except as shown in Figure 7.4.

• When penetrating a combustible wall, a wall shield

fi restop must be installed.

• When penetrating a combustible ceiling, a ceiling fi restop

must be installed.

• Horizontal runs of vent do not require vertical rise;

horizontal runs may be level.

NOTICE: ICON direct vent appliances require the use of
a vinyl soffi t shield (ICONDV-VSS) whenever the unit is
terminated horizontally in a home with vinyl siding.