E. vent diagrams, Top vent - horizontal termination, One elbow – Hearth and Home Technologies Direct Vent Gas Appliance CD4842MR User Manual

Page 23

background image

Heatilator • Caliber Mesh CD Series-SIT Valve • 4040-849 Rev J • 06/08

23

H

1

V

1

To replace the fi rst starter elbow with two 45° elbows,
refer to Figure 7.4. All other 90° elbows can be replaced
with two 45° elbows.
General Rules:
• SUBTRACT 3 ft. from the total H measurement for each

90° elbow installed horizontally.

• SUBTRACT 1-1/2 ft. from the total H measurement for

each 45° elbow installed horizontally.

• A maximum of three 90° elbows (or six 45° elbows)

may be used in any vent confi guration. Some elbows
may be installed horizontally. See Figure 7.9.

• Elbows may be placed back to back anywhere in the

system as long as the fi rst 90° elbow is a starter elbow
except as shown in Figure 7.4.

• When penetrating a combustible wall, a wall shield

fi restop must be installed.

• When penetrating a combustible ceiling, a ceiling

fi restop must be installed.

• Horizontal runs of vent do not require vertical rise;

horizontal runs may be level.

E. Vent Diagrams

Figure 7.3

One Elbow

1. Top Vent - Horizontal Termination

Note: The CD series appliances can adapt to SLP series
vent pipe when venting off the top of the appliance.
You must use a DVP-SLP24 adapter which can only
be attached to the appliance starting collar.

When looking at horizontal termination diagrams, the
adapter is not counted as part of the minimum vertical
(V

1

min.) requirements.

Whether horizontal or vertical termination, the adapter is
counted as part of the maximum vertical limitations.

All venting rules for the vent run must still be followed.

H

1

= 11 ft.

max.

V

1

= 1 ft.

DVP-SLP24

H

1

= 11 ft.

max

V

1

= 1 ft.

DVP

HORIZONTAL EXAMPLE

SLP

12 ft (3.66 m) min.

60 ft (18.29 m) max.

12 ft (3.66 m) min.

60 ft (18.29 m) max.

DVP

VERTICAL EXAMPLE

SLP

DVP-SLP24

Adapter

V

1

min.

V

1

max.

H

1

max.

ft

m

ft

m

ft

m

0

0.00

-

-

1.5

0.46

0.5

0.15

-

-

6

1.83

1

0.30

-

-

11

3.35

1.5

0.46

-

-

18

5.49

2

0.61

-

-

25

7.62

DVP

25

7.62

25

7.62

SLP

23

7.01

23

7.01

You may install a DVP elbow directly on top of the
CD4236M. The CD4842M requires the DVP6 vent
section prior to the elbow.