Honeywell VISTA-20P User Manual
Page 47
“A”
01 Zn List
1
Zone List
(prompt appears
if zone list was selected)
01-08 = zone list; [
∗] to continue
Enter the desired zone list number associated with this output number.
NOTE: Do not use pager zone lists 09-12 in output definitions.
Enter the zone list event that will activate this output.
Enter Event
0 = restore; 1 = alarm;
Alarm
1
2 = fault; 3= trouble
NOTE: For alarm, fault, and trouble, an event on ANY zone in the list activates the output,
but ALL zones in the list must be restored before the output is restored.
Press [
✱] to continue and skip to the “Output Action” prompt.
“B”
01 Enter Zn type
Perimeter 03
Zone Type
(prompt appears
if zone type was selected)
Enter the desired zone type associated with this output number. See below for a list of
available zone types.
CHOICES FOR ZONE TYPES:
00 = Not Used
05 = Day/Night
12 = Monitor Zone
01 = Ent/Exit #1
06 = 24 Hr Silent
14 = Carbon Monoxide
02 = Ent/Exit #2
07 = 24 Hr Audible
16 = Fire w/verification
03 = Perimeter
08 = 24 Hr Aux
23 = No Alarm Response
04 = Interior Follower
09 = Fire
24 = Silent Burglary
10 = Interior w/Delay 77 = Keyswitch Zone
81 = AAV Monitor Zone
90-91 = Configurable
CHOICES FOR SYSTEM OPERATION:
20 = Arming–Stay
36 = **At Bell Timeout***
52 = Kissoff
21 = Arming–Away
38 = Chime
54 = Fire Zone Reset
22 = Disarming
39 = Any Fire Alarm
58 = Duress
31 = End of Exit Time
40 = Bypassing
60 = AAV
32 = Start of Entry Time 41 = **AC Power Failure
66 = Function Key†
33 = Any Burglary Alarm 42 = **System Battery Low 67 = Bell Fail
43 = Comm. Failure
68 = Telco Line Cut
78 = Keyswitch Red LED
79 = Keyswitch Green LED
** Use 0 (Any) for Partition No. (P) entry.
*** Or at Disarming, whichever occurs earlier.
† Use *57 Menu Mode to assign the function key (function “07”).
Note: In normal operation mode:
Code + # + 7 + NN Key Entry starts Device NN.
Code + # + 8 + NN Key Entry stops Device NN.
Enter the partition in which this zone type will occur.
01 Partition
0 = any partition; 1 = partition 1;
Any partition
0
2 = partition 2; 3 = common
Press [
✱] to continue and skip to the “Output Action” prompt.
“C”
01 Enter Zn No.
12
Zone Number
(prompt appears
if zone number was selected)
Enter the desired zone number associated with this output number.
Press [
✱] to continue.
Enter the zone event that will activate this output.
01 Enter Event
0 = restore; 1 = alarm/fault/trouble
Restore 0
Press [
✱] to continue to the “Output Action” prompt
01 Output Action
Close for 2 sec
1
Output Action
0 = off
4 = Change Device State
1 = Close for 2 seconds
5 = Duration 1 (see data field *177)
2 = Stay Closed
6 = Duration 2 (see data field *177)
3 = Pulse on & off (1 sec ON, 1 sec OFF)
Enter the desired device action as listed above. Press the [
✱] key to continue.
Menu Mode Programming
5-11