A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance to

vent.

DO NOT pack insulation or other combustibles:

• Between ceiling fi restops

• Between wall shield fi restops

• Around vent system
Failure to keep insulation or other material away from

vent pipe may cause over heating and fi re.

8

Vent Clearances and Framing

B. Wall Penetration Framing

Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must

frame a hole for the wall shield fi restop(s). The wall shield

fi restop maintains minimum clearances and prevents cold

air infi ltration.
• The opening must be framed on all four sides using the

same size framing materials as those used in the wall

construction.

• A wall shield fi restop is required on one side only on in-

terior walls. If your local inspector requires a wall shield

fi restop on both sides, then both wall shield fi restops

must have a heat shield (refer to Section 16.B.) at-

tached to them.

• See Section 10.M. for information for regarding the in-

stallation of a horizontal termination cap.

Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncom-

bustible materials such as concrete, a hole with diameter

one inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall

shield fi restop is only required on one side and no heat

shield is necessary.

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

DVP heat shield - designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to

184 mm) thick

.

• If wall thickness is less than 4 in. the existing heat shields must be field trimmed.

If wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required.

3 in. (76 mm)

top clearance

1 in. (25 mm)

clearance

bottom & sides

Heat

Shield

Wall

Shield

Firestop

Heat

Shield

WALL

3 in. (76 mm)

top clearance

1 in. (25 mm)

clearance around

vertical sections

Figure 8.2 Exterior Wall Hole

* Shows center of vent framing hole for top venting. The center of the hole is

one (1) inch (25.4 mm) above the center of the horizontal vent pipe.

B

A

10 in.

12 in.

A*

B

73 -1/8 in. 72 -1/8 in.

Figure 8.1 Horizontal Venting Clearances To Combustible

Materials