Power specifications, Quickspecs, System specifications – HP ProLiant ML330 User Manual
Page 30
Part Number
319640-001
Spare Kit
324714-001
Operational Input Voltage Range
(Vrms)
90-264
Frequency Range (Nominal) (Hz)
47 - 63 (50 / 60)
Nominal Input Voltage (Vrms)
100
115
208
220
230
240
Max Rated Output Wattage Rating
300
300
300
300
300
300
Nominal Input Current (Arms)
4.6
3.9
2.1
2.0
1.9
1.8
Max Rated Input Wattage Rating
(Watts)
435
429
423
423
417
411
Max. Rated VA (Volt-Amp)
458
451
445
445
439
433
Efficiency (%)
69
70
71
71
72
73
Power Factor
0.95
Leakage Current (mA)
0.70
0.81
1.47
1.55
1.62
1.69
Maximum Inrush Current (A peak)
42
48
81
92
96
100
Maximum Inrush Current duration
(mS)
2
System Specifications
Processor
Memory
HDD
PCI
PS
HP ProLiant ML330 G3 Fully Configured
2
4
5
4
1
Fully Loaded System Input Wattage (W)
425
419
413
413
408
402
Fully Loaded System Input Current
(Arms)
4.5
3.8
2.1
2.0
1.9
1.8
Fully Loaded System Thermal (BTU-Hr)
1450
1429
1409
1409
1390
1371
Fully Loaded System VA (Volt-Amp)
448
441
435
435
429
423
System Leakage with all power supplies
loaded (mA)
0.70
0.81
1.47
1.55
1.62
1.69
System Inrush Current with all power
supplies loaded (A)
42
48
87
92
96
100
Power cord requirements
Nema 5-15P to IEC320-C13
Option no./Spare no: 227099-
001/187335-001
IEC320-C13 to IEC320-C14
Option no./Spare no: 142257-
001/142258-B21
Example of real input watts consumed versus rated watts consumed is available via the online tool located at url:
select system calculator for one of the systems and reference the green fields at the bottom of the calculator.
NOTES:
* To review typical system power ratings use the Active Answers Power Calculator which is available via the online tool
To drill down to calculators:
- Click on: "ProLiant Servers"
- Click on the Server of interest. Example: ML330 G3
- Click on: "Power Calculator" link (You may need to scroll down to see it.)
QuickSpecs
HP ProLiant ML330 Generation 3
Power Specifications
DA - 11614 Worldwide QuickSpecs — Version 44 — 6.28.2005
Page 30