beautypg.com

1 routine inspection (daily/weekly), 2 periodic inspection (six monthly), 3 re-lubrication – HP 8-UB-1 User Manual

Page 21

background image

UB USER INSTRUCTIONS ENGLISH 71569247 07-04

Page 21 of 32

®

Our specialist service personnel can help with
preventative maintenance records and provide
condition monitoring for temperature and vibration to
identify the onset of potential problems.

If any problems are found the following sequence of
actions should take place:
a) Refer to section 7, Faults; causes and remedies,

for fault diagnosis.

b) Ensure equipment complies with the

recommendations in this manual.

c) Contact Flowserve if the problem persists.

6.2.1 Routine inspection (daily/weekly)

The following checks should be made

and the appropriate action taken to remedy any
deviations:
a) Check operating behaviour. Ensure noise,

vibration and bearing temperatures are normal.

b) Check that there are no abnormal fluid or

lubricant leaks (static and dynamic seals) and
that any sealant systems (if fitted) are full and
operating normally.

c) Check that shaft seal leaks are within acceptable

limits.

d) Check the level and condition of oil lubricant. On

grease lubricated pumps, check running hours
since last recharge of grease or complete grease
change.

e) Check any auxiliary supplies eg. heating/cooling,

if fitted, are functioning correctly.

Refer to the manuals of any associated

equipment for routine checks needed.

6.2.2 Periodic inspection (six monthly)

a)

Check foundation bolts for

security of attachment and corrosion.

b) Check pump running records for hourly usage to

determine if bearing lubricant requires changing.

c) The coupling should be checked for correct

alignment and worn driving elements.

Refer to the manuals of any associated

equipment for periodic checks needed.

6.2.3 Re-lubrication
Lubricant and bearing temperature analysis can be
useful in optimizing lubricant change intervals. In
general however, the following is recommended.

See section 5.2.1 for grease

recommendations.

Regrease - via grease nipples every 2 000 hours or
sooner depending on the severity of the application.

a) It is important not to under or over grease the

bearings as this will lead to over heating and
premature failure. Grease lubricated bearing
housings have grease nipples fitted in the
bearing brackets.

b) The maximum allowable operating temperatures

for anti friction bearings will vary from unit to unit,
depending on ambient and fluid temperature.
The rise above ambient should not normally
exceed 55

°C (131 °F) or a combined maximum

of 95

°C (204 °F).

c) A continuously rising temperature or an abrupt

temperature rise indicates a problem. If these
symptoms occur, stop the pump immediately and
investigate the cause.

TIME

T

E

MPERAT

URE

Grease change - every 4 000 hours or sooner
depending on the severity of the application.
a) Remove the bearing bracket from the rotor

assembly.

b) Brush the bearing bracket with hot kerosene (100 to

115 °C/212 to 240 °F) or other non-toxic solvent.

c) Clean and flush out the housing with a light

mineral oil.

d) Do not use waste oil to clean the housing.

To clean the bearings:
a) Wipe off as much grease as possible with a clean

lint-free cloth.

b) Brush bearings with hot kerosene (80 to 90 °C/

175 to 195 °F) while gently spinning the outer
bearing ring.

c) Spin each ball to ensure that it is clean.