Instructional booklet, Warning, Fixed and drawout magnum transfer switches – Eaton Electrical Magnum Transfer Switch User Manual

Page 26

background image

For more information visit: www.Eaton.com

IB01602011E

Instructional Booklet

Page 26

Effective: March 2007

Fixed and Drawout Magnum Transfer Switches

Figure 36. Magnum Bypass Lights.
The right door control panel has the following standard features:

1. Light to indicate if the Source 1 switching device is isolated

(only if the Source 1 switching device is racked out).

2. Light to indicate if the Source 2 switching device is isolated

(only if the Source 2 switching device is racked out).

3. Light to indicate if the Source 1 bypass switching device is

closed.

4. Light to indicate if the Source 2 bypass switching device is

closed.

7.2 Automatic Operation

The intelligence/supervisory circuits on Eaton transfer switches

constantly monitor the condition of both the Source 1 and Source

2 power sources. These circuits automatically initiate an immedi-

ate transfer of power from the Source 1 to the Source 2 power

source when the power source fails or the voltage level drops

below a preset value. Transfer back to the Source 1 power

source is automatic upon return of the Source 1 power source.
Monitoring the power source is always performed on the line side

of the power source to which the switch is connected. The

Source 1 power source is the preferred source and the transfer

switch will always seek this source when it is available.

7.3 Bypassing the Transfer Switch

7.3.1 Source 1 to Source 1 BYPASS
The Source 1 switching device can be bypassed and isolated by

the following sequence (Figures 36 and 37):
1. Move the generator selector switch to the OFF position to

avoid nuisance starts.

2. Close the Source 1 bypass switch manually. The Source 1

bypassed light will illuminate.

3. Open and rack out the Source 1 switching device (see Section

6). The Source 1 isolated light will illuminate and the Source 1

position energized light will no longer be illuminated.

4. Inspect and/or perform the needed maintenance on the Source

1 switching device.

5. Rack in the Source 1 switching device (see Section 6). The

Source 1 switching device will automatically recharge and

close when it is in the CONNECT position. The Source 1 iso-

lated light will no longer be illuminated, but the Source 1 posi-

tion energized light will be illuminated.

6. Open the Source 1 bypass switch. The Source 1 bypassed

light will no longer be illuminated.

7. The Source 1 switching device is now back in automatic oper-

ation.

7.3.2 Source 2 TO Source 2 BYPASS
The Source 2 switching device can be bypassed and isolated by

the following sequence:
1. Move the generator selector switch to the RUN position to

avoid losing power.

2. Close the Source 2 bypass switching device manually. The

Source 2 bypass light will illuminate.

3. Open and rack out the Source 2 switching device

(see Section 6). The Source 2 isolated light will illuminate and

the Source 2 position energized light will no longer be illumi-

nated.

4. Inspect and/or perform the needed maintenance on the Source

2 switching device.

5. Rack in the Source 2 switching device (see Section 6). The

Source 2 switching device will automatically recharge and

close when in the CONNECT position. The Source 2 isolated

light will no longer be illuminated, and the Source 2 position

energized light will illuminate.

6. Open the Source 2 Bypass switch. The source 2 Bypass light

will no longer be illuminated.

7. The Source 2 Switch is now back in automatic operation.

WARNING

THE CLOSED TRANSITION PRODUCT CONTAINS A SPECIAL CON-

TACT ARRANGEMENT (OVERLAPPING CONTACTS). MISUSE CAN

RESULT IN DEATH, SEVERE PERSONAL INJURY, AND/OR PROPERTY

DAMAGE.