Fixed and Drawout Magnum Transfer Switches

Figure 24. Close Switch by Pushing Close Button.

5.2 Automatic Transfer Switch

The operating sequence of an ATS is dictated by the switch’s

standard features and selected options. Operation of an ATS dur-

ing Source 1 power source failure, Source 1 power source restora-

tion, and testing is described in the associated Controller

Instruction Booklet.

Figure 25. Switching Device Closing Precautions (Closed Transition Only).

NOTICE

IF A TRANSFER SWITCH WITH ANY TYPE OF ELECTRICAL OPERAT-

ING CAPABILITIES IS TO BE OPERATED MANUALLY UTILIZING THE

MANUAL OPERATING HANDLE, IT IS STRONGLY RECOMMENDED

THAT THE TRANSFER CONTROL CIRCUIT FIRST BE ISOLATED. THIS

IS ACCOMPLISHED BY DISCONNECTING THE S7/P7 PLUG ON THE

TRANSFORMER PANEL. AN AUTOMATIC ENGINE START WILL

OCCUR UNLESS THE GENERATOR RUN SWITCH SET TO “OFF.” IF,

HOWEVER, A TRANSFER SWITCH IS SUPPLIED WITH A FOUR-POSI-

TION SELECTOR SWITCH (OPTION 6H), IT CAN BE TURNED TO THE

OFF POSITION, MAKING IT UNNECESSARY TO UNPLUG THE LOGIC.

IN THE CASE OF THE ATS DESIGN, ANY ATTEMPT TO OPERATE

THE MANUAL HANDLE WITHOUT FIRST ISOLATING THE CONTROL

CIRCUIT CAUSES AN AUTOMATIC TRANSFER.

Follow Manual Operation Instructions Below

switching devices simultaneously

can cause severe injury

Attempting to close both

or death.

WARNING

2. Open both switching devices

Manual Operation Instructions

4. Verify source availability
5. Close switching device on available

source

1. Disconnect Logic Connectors

3. Verify "OPEN" flags

7805C60H05

MANUAL CLOSE BUTTON

Operating Instructions

Do Not Use Without

Reading Manual

OVERLAPPING CONTACTS

must be Synchronized

SOURCE 1 AND SOURCE 2

WARNING

7805C60H04

THIS PRODUCT CONTAINS A SPECIAL CON-
TACT ARRANGEMENT (OVERLAPPING CON-
TACTS). MISUSE CAN RESULT IN DEATH
SEVERE PERSONAL INJURY OR PROPERTY
DAMAGE.

(THIS LABEL IS APPLIED TO THE DOOR )

FOLLOW THE INSTRUCTIONS
OUTLINED IN THE NEXT
WARNING LABEL.

(THIS LABEL IS APPLIED TO
THE COVER OF THE MANUAL
CLOSE BUTTON ON EACH

THESE INSTRUCTIONS ONLY PERTAIN TO
MANUALLY CLOSING A SINGLE SWITCHING
DEVICE. ATTEMPTING TO CLOSE BOTH
SWITCHING DEVICES CAN CAUSE SEVERE
INJURY OR DEATH.

THIS LABEL IS APPLIED TO THE DOOR.