IB01602011E

Instructional Booklet

Page 2

Effective: March 2007

Fixed and Drawout Magnum Transfer Switches

Figure 1. Typical Automatic Transfer Switch Equipment Nameplate.

Step 1: Remove any dirt or debris that may have collected during

shipment or installation. NEVER use high pressure blow-

ing air. This could drive dirt or other foreign objects into

electrical or mechanical components which could cause

damage. Use an industrial quality vacuum cleaner to

remove any dirt or foreign objects.

Step 2: Be certain all cable connections are correct and that the

phase rotation of both sources match.

Step 3: Inspect the engine start connections and verify the cor-

rect connection of all control wires.

Step 4: Check all programmable setpoints and adjust as neces-

sary. In addition, adjust any optional accessories as

required.

Step 5: Be certain that the actual lug torque values are in keeping

with the requirements outlined in the instruction book to

insure the integrity of power connections.

Step 6: Check to be sure that all covers and barriers are properly

installed and fastened.

ALL POSSIBLE CONTINGENCIES WHICH MAY ARISE DURING INSTALLATION, OPERATION, OR MAINTENANCE, AND ALL DETAILS AND VARIA-

TIONS OF THIS EQUIPMENT DO NOT PURPORT TO BE COVERED BY THESE INSTRUCTIONS. IF FURTHER INFORMATION IS DESIRED BY THE

PURCHASER REGARDING HIS PARTICULAR INSTALLATION, OPERATION, OR MAINTENANCE OF PARTICULAR EQUIPMENT, CONTACT AN

EATON REPRESENTATIVE.

WARNING

READ AND UNDERSTAND THE INSTRUCTIONS CONTAINED HEREIN-

AFTER BEFORE ATTEMPTING TO UNPACK, ASSEMBLE, OPERATE,

OR MAINTAIN THIS EQUIPMENT.

HAZARDOUS VOLTAGES ARE PRESENT INSIDE TRANSFER SWITCH

ENCLOSURES THAT CAN CAUSE DEATH OR SEVERE PERSONAL

INJURY. FOLLOW PROPER INSTALLATION, OPERATION, AND MAIN-

TENANCE PROCEDURES TO AVOID THESE VOLTAGES.

TRANSFER SWITCH EQUIPMENT COVERED BY THIS INSTRUCTION

BOOK IS DESIGNED AND TESTED TO OPERATE WITHIN ITS NAME-

PLATE RATINGS. OPERATION OUTSIDE OF THESE RATINGS MAY

CAUSE THE EQUIPMENT TO FAIL RESULTING IN DEATH, SERIOUS

BODILY INJURY, AND/OR PROPERTY DAMAGE. ALL RESPONSIBLE

PERSONNEL SHOULD LOCATE THE DOOR MOUNTED EQUIPMENT

NAMEPLATE AND BE FAMILIAR WITH THE INFORMATION PROVIDED

ON THE NAMEPLATE. A TYPICAL EQUIPMENT NAMEPLATE IS

SHOWN IN FIGURE 1.

NOTICE

A FINAL INSPECTION OF THE EQUIPMENT SHOULD BE PERFORMED

PRIOR TO ENERGIZING THE TRANSFER SWITCH.

E

Automatic Transfer Switch

Cat No: ATVIMGB33200XRU 11/04
GO No: 1of1
Item 1

Poles: 3 Amps: 3200 Volt: 120/600 VAC
Phase: 3 Hertz: 60 Wire: 4