Remote i/o configuration – ProSoft Technology AN-X-AMX User Manual
Page 45

AN-X-AMXRIO Page
41
Remote I/O Configuration
To set the remote I/O configuration using the web interface, the remote I/O network must
be connected to the AN-X-AMXRIO. The ControlLogix with the exclusive owner
connection must be in program mode.
Start your web browser and enter the AN-X IP address as the address.
Select Configure AutoMax RIO Ethernet/IP.
Click on the link Automatically generate an AutoMax configuration file. The AN-X-
AMXRIO module reads the current network configuration and stores it.
When the autoconfiguration is done, the web interface displays a summary of the network
found and displays the message Automatic configuration done. Click the Back to
configuration page
link.
To view the configuration file that has been created, click the View AutoMax RIO
Ethernet/IP Configuration
link. The configuration is displayed either in a spreadsheet or
as a text file.
TIP
To view the current configuration, it may be necessary to refresh the
displayed configuration once or twice, as the browser may use a