ProSoft Technology AN-X-AMX User Manual
Page 25

AN-X-AMXRIO Page
21
Input and Output Data
The tag file contains the location of the scheduled input and output data for all I/O
modules and registers. When you import the tag file into RSLogix 5000, you can use the
tags to refer to I/O data.
Refer to page 26 for detailed information on the tag file format.
Status Input Data
The status input data consists of the following diagnostic data.
Offset
Description
0
Drop status, 1 = good, 0 = bad or not present
Bit 1 = drop 1, bit 7 = drop 7, etc
1
Drop 1 extended status
0 = OK, 1 = No response, 2 = Configuration mismatch,
3=Length error, 4 = mask error
2
Drop 2 extended status
3
Drop 3 extended status
4
Drop 4 extended status
5
Drop 5 extended status
6
Drop 6 extended status
7
Drop 7 extended status
8
Transmit count
9
Receive count
10
Receive protocol errors
11
Receive noise
12
Receive timeout
13
Receive CRC error
14
Receive overrun
15
Receive abort
16
ControlLogix output average update time for previous 100
updates
17
ControlLogix output minimum update time for previous 100
updates
18
ControlLogix output maximum update time for previous 100
updates
19
ControlLogix output maximum update time since connection
opened