Remote I/O Adapter Status and Error Data
RIO ♦ ProLinx Gateway
Driver Manual
Rockwell Automation® Remote I/O Adapter
ProSoft Technology, Inc.
Page 23 of 39
February 4, 2010
5
Remote I/O Adapter Status and Error Data
In This Chapter
Remote I/O Adapter Error Codes .......................................................... 24
The second and most thorough troubleshooting method is the powerful Debug
port on the module which provides much more complete access to the internal
operation and status of the module. Accessing the Debug capabilities of the
module is accomplished easily by connecting a PC to the Debug port and loading
a terminal program such as ProSoft Configuration Builder or HyperTerminal.
The following topics list the register addresses that contain error and status data.
Use the Database View option from the ProLinx Main Menu to view the contents
of each register. The ProLinx Reference Guide provides information on using this
option.
The module uses internal database addresses from 9000 through 9013.
Addresses 9014 through 9099 contain no valid data.
The data area is initialized with zeros whenever the module is initialized. This
occurs during a cold-start (power-on), reset (reset push-button pressed) or a
warm-boot operation (commanded or loading of new configuration).
Example Internal
Database Address
Word Offset
Description
9000
0
Output/Reset Command Count (1|7)
9001
1
Output Command Count
9002
2
BTW Received Count
9003
3
Communication Failure Count
9004
4
BTW Processed Block Count
9005
5
BTW Parsed Block Count
9006
6
BTW Command Control Count
9007
7
BTW Bad Block Number Count
9008
8
BTW Bad Data Size Count
9009
9
BTR Block Built Count
9010
10
BTR Request Block Count
9011
11
Read Image Update Count
9012
12
Current RIO Error Code
9013
13
Last RIO Error Code
9014
14
No Valid Data
---
9099