Troubleshooting the Remote I/O adapter communication modules can be
performed using several methods.

The first and quickest is to scan the LEDs on the module to determine the
existence and possibly the cause of a problem. This section provides insight into
the operation of the Remote I/O status LED. The ProLinx Reference Guide
provide information on the module’s other LEDs.

4.1

Remote I/O Interface

LED Color

Description

Off

No communication detected on the Remote I/O link. Verify
connection to scanner, power, and use Debug terminal capabilities.

Green
Flashing

Remote adapter not actively controlling I/O (Scanner to adapter
communication link is normal). Verify if the processor is in program,
or duplicate node address on network.

ACTIVE

Green Solid

Normal indication. Remote I/O adapter is operational. Check base
module APPERR led to be sure