RIO ♦ ProLinx Gateway

RIO Protocol Configuration

Rockwell Automation® Remote I/O Adapter

Driver Manual


Page 20 of 39

ProSoft Technology, Inc.

February 4, 2010

3.2.8 Last

Rack

Yes or No

This parameter specifies if the module is the last rack. A value of Yes signifies
the module is the last rack, and a value of No indicates the module is not the last
rack.

3.2.9 Data

Rate

57,115,230

This parameter specifies the data transfer rate to be used on the RIO interface.
Valid values for the parameter are as follows: 57 = 57K baud, 115 = 115K baud
and 230 = 230K baud. Invalid entries for this parameter will automatically set the
data rate to 57K baud.

3.2.10 Input Word 1 ... 7

0 to 3999

This parameter specifies the virtual database address to be associated with the
input value. The module will constantly update the Input word value with the data
stored in the register selected.

3.2.11 Output Word 1 ... 7

0 to 3999

This parameter specifies the virtual database address to be associated with the
output value. The module will constantly update the database register selected
with the data present in the Output Image word.

3.3

Remote I/O Adapter Cable Connection

1

2

Blue Shield Clear

ACTIVE

1

2

Blue Shield Clear

ACTIVE

The RIO interface uses the standard Belden 9463 (Blue Hose) cable and is
terminated as described in the Rockwell Automation Remote I/O documentation.

No termination resistor is provided on the RIO adapter communication card,
therefore any necessary termination resistance must be applied via the screw
terminal connector.