3.2.4 BTW Register Count
0 to 4000
This parameter specifies the number of words to be accepted using the BTW
operation. Each block received by the module can contain up to 60 words of
data.
3.2.5 Rack
Size
0 to 3
This parameter specifies the rack size that the module is to emulate. The code
values entered represent the following rack sizes: 0=1/4 rack, 1=1/2 rack, 2=3/4
rack and 3=full rack. The rack size determines the number of input and output
words.
3.2.6 Rack
Number
0 to 63
This parameter specifies the rack number of the RIO interface. Valid entries are 0
to 63 and the number must be unique on the RIO network.
The following table describes the relationship between the Rack Number
parameter in the module (decimal), and the corresponding octal value in the
PLC5 processor.
Prolinx
(decimal)
PLC5
(octal)
Prolinx
(decimal)
PLC5
(octal)
Prolinx
(decimal)
PLC5
(octal)
Prolinx
(decimal)
PLC5
(octal)
0 0 16 20 32 40 48 60
1 1 17 21 33 41 49 61
2 2 18 22 34 42 50 62
3 3 19 23 35 43 51 63
4 4 20 24 36 44 52 64
5 5 21 25 37 45 53 65
6 6 22 26 38 46 54 66
7 7 23 27 39 47 55 67
8 10 24 30 40 50 56 70
9 11 25 31 41 51 57 71
10 12 26 32 42 52 58 72
11 13 27 33 43 53 59 73
12 14 28 34 44 54 60 74
13 15 29 35 45 55 61 75
14 16 30 36 46 56 62 76
15 17 31 37 47 57 63 77
3.2.7 Group
Number
0,2,4,6
This parameter specifies the group number for the RIO interface. Valid entries
are 0, 2, 4 and 6.