ProSoft Technology 5201-DFNT-BACNET User Manual
Page 40

Client Error/Status Data
BACnet ♦ ProLinx Gateway
Protocol Manual
BACnet/IP Client Edition 2
Page 40 of 52
ProSoft Technology, Inc.
November 24, 2010
Command List Parsing
Error Word
MSB
LSB
Group
Description
0xFF
0x01
Command
Param
Error while reading in a command. Not enough parameters are
present in the current command record to construct a command.
0xFF
0x02
Command
Param
Invalid type code entered for the enable field. Only values of 0 to
2 are accepted.
0xFF
0x03
Command
Param
Count value in command set to zero. This parameter must be set
to a value greater than or equal to 1 and less than 25.
0xFF
0x04
Command
Param
Invalid swap code entered for command. Values of 0 to 3 are only
those accepted by the program.
0xFF
0x05
Command
Param
Invalid function code entered. This parameter must have one of
the following values: 12, 14, 15 or 16.
0xFF
0x06
Command
Param
Invalid datatype selected for the command. This parameter must
be set to one of the following values: 0=analog input, 1=analog
output, 3=binary input or 4=binary output.
0xFF
0x07
Command
Param
Invalid property value for the command. Refer to the property list
for all available properties supported by the program. This does
not imply that all servers will contain this property for every object
type.