beautypg.com

ProSoft Technology 5201-DFNT-BACNET User Manual

Page 40

background image

Client Error/Status Data

BACnet ♦ ProLinx Gateway

Protocol Manual

BACnet/IP Client Edition 2

Page 40 of 52

ProSoft Technology, Inc.

November 24, 2010

Command List Parsing

Error Word

MSB

LSB

Group

Description

0xFF

0x01

Command

Param

Error while reading in a command. Not enough parameters are

present in the current command record to construct a command.

0xFF

0x02

Command

Param

Invalid type code entered for the enable field. Only values of 0 to

2 are accepted.

0xFF

0x03

Command

Param

Count value in command set to zero. This parameter must be set

to a value greater than or equal to 1 and less than 25.

0xFF

0x04

Command

Param

Invalid swap code entered for command. Values of 0 to 3 are only

those accepted by the program.

0xFF

0x05

Command

Param

Invalid function code entered. This parameter must have one of

the following values: 12, 14, 15 or 16.

0xFF

0x06

Command

Param

Invalid datatype selected for the command. This parameter must
be set to one of the following values: 0=analog input, 1=analog

output, 3=binary input or 4=binary output.

0xFF

0x07

Command

Param

Invalid property value for the command. Refer to the property list
for all available properties supported by the program. This does

not imply that all servers will contain this property for every object

type.