BACnet Client 0
The BACnet Client 0 section of the configuration specifies the parameters for the
BACnet Client to be emulated on the gateway. The command list for the Client is
entered in a separate section.
3.2.1 Minimum Command Delay
0 to 32767
This parameter specifies the number of milliseconds to wait between the initial
issuances of a command. It can be used to delay all commands sent to servers
to avoid "flooding" the network. This parameter does not affect retries of a
command, as they are issued when failure is recognized.
3.2.2 Response Timeout
0 to 65535 milliseconds
This is the time in milliseconds that a Client will wait before re-transmitting a
command if no response is received from the addressed server. The value to use
depends on the type of communication network used, and the expected
response time of the slowest device on the network.
3.2.3 Retry Count
0 to 10
This parameter specifies the number of times a command will be retried if it fails.