BACnet ♦ ProLinx Gateway
Client Error/Status Data
BACnet/IP Client Edition 2
Protocol Manual
ProSoft Technology, Inc.
Page 37 of 52
November 24, 2010
4.2
BACnet Client Command List Error Data
Each command in the command list for the BACnet Client has a reserved word
value for a status/error code. This error data list can be read using the
Debug/Config Port and can be placed in the gateway's internal database.
The first word in the register location defined contains the status/error code for
the first command in the Client's command list. Each successive word in the
command error list is associated with the next command in the list. Therefore, the
size of the data area depends on the number of commands defined. The
structure of the data area is displayed in the following tables.
4.2.1 BACnet Client 0 (Command List Error Data)
Internal Database
Address
Offset
Description
12310
0
Command #0 Error Status
12311
1
Command #1 Error Status
12312
2
Command #2 Error Status
12313
3
Command #3 Error Status
12314
4
Command #4 Error Status
.
.
.
.
.
.
12407
97
Command #97 Error Status
12408
98
Command #98 Error Status
12409
99
Command #99 Error Status
Note that the values in the Command List Error Status tables are initialized to
zero (0) at power-up, cold boot and during warm boot. Refer to the following topic
containing Error Codes to interpret the status/error codes present in the data
area.