Client Error/Status Data

BACnet/IP Client Edition 2

Protocol Manual

ProSoft Technology, Inc.

Page 37 of 52

November 24, 2010

4.2

BACnet Client Command List Error Data

Each command in the command list for the BACnet Client has a reserved word

value for a status/error code. This error data list can be read using the

Debug/Config Port and can be placed in the gateway's internal database.
The first word in the register location defined contains the status/error code for

the first command in the Client's command list. Each successive word in the

command error list is associated with the next command in the list. Therefore, the

size of the data area depends on the number of commands defined. The

structure of the data area is displayed in the following tables.

4.2.1 BACnet Client 0 (Command List Error Data)

Internal Database
Address

Offset

Description

12310

0

Command #0 Error Status

12311

1

Command #1 Error Status

12312

2

Command #2 Error Status

12313

3

Command #3 Error Status

12314

4

Command #4 Error Status

.

.

.

.

.

.

12407

97

Command #97 Error Status

12408

98

Command #98 Error Status

12409

99

Command #99 Error Status


Note that the values in the Command List Error Status tables are initialized to

zero (0) at power-up, cold boot and during warm boot. Refer to the following topic

containing Error Codes to interpret the status/error codes present in the data

area.