Functional Overview

BACnet ♦ ProLinx Gateway

Protocol Manual

BACnet/IP Client Edition 2

Page 16 of 52

ProSoft Technology, Inc.

November 24, 2010

2.1

BACnet/IP Client

General

One UDP Client

Command List

Support for 100 commands, each configurable for
command, IP address, register to/from addressing

and word/bit count.

Service Port

1 to 65535

Function Code

12=Read Single Property
14=Read Multiple Properties
15=Write Single Property
16=Write Multiple Properties

Data Type

0=Analog Input
1=Analog Output
2=Analog Value
3=Binary Input
4=Binary Output
5=Binary Value

Point Count

1 to 25


The gateway supports a single independent Client on the IP network using the

UDP protocol to interface with processors or devices using a user constructed

command list of up to 100 entries. The gateway's internal database is used as

the source for write commands to the remote units. Data collected from the

remote units using read commands is placed in the gateway's database.

2.1.1 Module Internal Database

The internal database is central to the functionality of the gateway. This database

is shared between all the drivers in the gateway and is used as a conduit to pass

information from one device on one network to one or more devices on another

network. This permits data from devices on one communication port to be viewed

and controlled by devices on another port.
In addition to data from the Client, status and error information generated by the

gateway can also be mapped into the internal database. Use this data to

determine the "health" of the gateway and to determine if commands are being

processed successfully.

This manual is related to the following products: