ProSoft Technology 5201-DFNT-BACNET User Manual
Page 16

Functional Overview
BACnet ♦ ProLinx Gateway
Protocol Manual
BACnet/IP Client Edition 2
Page 16 of 52
ProSoft Technology, Inc.
November 24, 2010
2.1
BACnet/IP Client
General
One UDP Client
Command List
Support for 100 commands, each configurable for
command, IP address, register to/from addressing
and word/bit count.
Service Port
1 to 65535
Function Code
12=Read Single Property
14=Read Multiple Properties
15=Write Single Property
16=Write Multiple Properties
Data Type
0=Analog Input
1=Analog Output
2=Analog Value
3=Binary Input
4=Binary Output
5=Binary Value
Point Count
1 to 25
The gateway supports a single independent Client on the IP network using the
UDP protocol to interface with processors or devices using a user constructed
command list of up to 100 entries. The gateway's internal database is used as
the source for write commands to the remote units. Data collected from the
remote units using read commands is placed in the gateway's database.
2.1.1 Module Internal Database
The internal database is central to the functionality of the gateway. This database
is shared between all the drivers in the gateway and is used as a conduit to pass
information from one device on one network to one or more devices on another
network. This permits data from devices on one communication port to be viewed
and controlled by devices on another port.
In addition to data from the Client, status and error information generated by the
gateway can also be mapped into the internal database. Use this data to
determine the "health" of the gateway and to determine if commands are being
processed successfully.