Client Error/Status Data

BACnet ♦ ProLinx Gateway

Protocol Manual

BACnet/IP Client Edition 2

Page 36 of 52

ProSoft Technology, Inc.

November 24, 2010

4.1

Client Error/Status Data

The Client connection Error and Status Data areas are discussed in this section
The error/status data table is located at a virtual address assigned by ProLinx. If

this data is moved to the gateway's database using the gateway's data mapping

feature, it will be available to the other protocol supported on the gateway. If it is

not mapped into the gateway's database, the data will only be available through

the Configuration/Debug Port.
The data area is initialized with zeros whenever the module is initialized. This

occurs during a cold-start (power-on), reset (reset push-button pressed) or a

warm-boot operation (commanded or loading of new configuration).

Note: The ProLinx Reference Guide contains detailed information on accessing the contents of the
following registers.

4.1.1 BACnet Client 0 Status

The following table lists the data areas that can be mapped from the virtual

addresses into the gateway's internal database.

Status Register

Description

12300

Command Request Count

12301

Command Response Count

12302

Command Error Count

12303

Number of Request Packets

12304

Number of Response Packets

12305

Errors Sent

12306

Errors Received

12307

Configuration Error Word

12308

Current Error

12309

Last Error

12310 to 12409

Command List Errors (1 word register for each command)

12410 to 12499

No Valid Data