ProSoft Technology MVI46-MBP User Manual
Page 73

Reference MVI46-MBP
♦ SLC Platform
Modbus Plus Communication Module
ProSoft Technology, Inc.
Page 73 of 101
February 19, 2008
DB
Address
Modbus
Address
Parameter Description
5090 45091 Enable
This parameter is used define if the command will
be executed or will be disregarded. The following
values are valid: 0=Disables the command and it
will not execute; 1=The command will be
considered for execution each scan of the
command list and will be controlled by the PollInt
parameter; and 2=The command will only execute
if the event control bit for the command is set.
5091 45092 Module's
Database
Register Number
This parameter specifies the starting internal
register address to be associated with the
command. Valid entry for this parameter is 0 to
3999.
5092 45093 Polling
Interval
This parameter defines the minimum number of
seconds to wait between the execution of
continuous commands (Enable=1). This poll
interval command can be used to lighten the
communications load on a busy network. Valid
entry for this parameter is 0 to 65535.
5093 45094 Register
Count
This parameter defines the number of registers to
be considered by the command. Valid entry for
this parameter is 1 to 100.
5094 45095 Swap
Code This parameter is not implemented in the current
version of the software but will be used in the
future to swap the bytes of word and double-word
values when floating-point data is required.
5095 45096 Device
Index This parameter associates the command with a
device defined in the device definition table
(Device[ ] in the MBPlusModuleDef object). The
index defined in this parameter sets the route path
defined for the device in the Modbus Plus
message.
5096 45097 Function
Code
This parameter specifies the function to be
performed by the command. Valid entries are 3=
Read register data from a node and 16= Write
register data to a node.
5097 45098 Register Address
in Device
This parameter defines the starting address in the
device being considered by the command. Values
entered in this field are dependent on the node's
database definition. Refer to the specific
manufacture's database definition for the device to
determine the location of the data to be interfaced.
5098 45099 Spare
Not
used
5099 45100 Spare
Not
used