Modbus plus communication port, Database definition, Module memory map – ProSoft Technology MVI46-MBP User Manual
Page 60: Overview, Database, Definition, 6 modbus plus communication port, 7 database definition

MVI46-MBP ♦ SLC Platform
Reference
Modbus Plus Communication Module
Page 60 of 101
ProSoft Technology, Inc.
February 19, 2008
5.6
Modbus Plus Communication Port
The MVI46-MBP module has two physical Modbus Plus connectors with two DB-
9 Female plugs located on the front of the module.
5.7 Database
Definition
This section contains a listing of the internal database of the MVI46-MBP
module. This information can be used to interface other devices to the data
contained in the module.
5.7.1 Module Memory Map
Overview
Access
Module Address
Range
Modbus Address
Range
Description Block
Low
High
Low
High
Size
R/W 0
3999 40001
44000 Data
Registers
4000
R
4000
4069
44001
44070
Global In Update Status
70
R
4070
4269
44071
44270
Master Command Status
200
R
4270
4299
44271
44300
Misc Module Status
30
R
4300
4369
44301
44370
Global In Update Counters
70
R/W
4370
4409
44371
44410
Module Configuration Block
40
R/W
4410
4449
44411
44450
Global In File Map
40
R/W 4450 5089 44451
45090 Device
Definition
640
R/W
5090
7089
45091
47090
Master Command List
2000
O File
7090
7129
47091
47130
Global Out Image
40
I File
7130
7169
47131
47170
Global In Image
40
R
7170
7221
47171
47222
Command Event Data
52
The Data Registers area holds data collected from other nodes on the network
(master read commands or global input data) or data received from the
processor (write blocks). Additionally, this data area is used as a data source for
the processor (read blocks) or other nodes on the network (master write