Error code definition, Miscellaneous module status – ProSoft Technology MVI46-MBP User Manual
Page 63

Reference MVI46-MBP
♦ SLC Platform
Modbus Plus Communication Module
ProSoft Technology, Inc.
Page 63 of 101
February 19, 2008
Error Code Definition
High Byte
Low Byte
Description
0x00
0x00
Normal - Driver will reset when processing command
0x01
Command has completed successfully
0x02
Routing
Errors
0x01
No response received - Is addressed unit online
0x02
program access denied
0x04
exception response received
0x08
invalid node type in routing path
0x10
slave rejected the Modbus command - invalid input path??
0x20
initiated transaction forgotten by slave
0x40
unexpected master output path received
0x80
unexpected response received
0x04
Configuration
Errors
0x01
Invalid Configuration for Command
0x02
Invalid Command Type - 1 = Write, 2 = Read , All other error
0x04
0x08
0x10
0x20
0x40
0x80
Miscellaneous Module Status
Element DB
Address
Description
0
4270
Module Status - Software Reset Response
1 4271
Peer
Status
2
4272
Token Pass Counter
3
4273
Token Rotation Time in milliseconds
4 4274-H
Communication
Failed Error Counter
4
4274-L
Communication Retry Counter
5
4275-H
No Response Received Error Counter
5
4275-L
Good Received Packet Success Counter
6
4276-H
Unexpected Path Error Counter
6
4276-L
Exception Response Received Error Counter
7
4277
Data master output path 1 & 2 counter
8
4278
Data master output path 3 & 4 counter
9
4279
Data master output path 5 & 6 counter
10
4280
Data master output path 7 & 8 counter
11
4281
Data slave output path 1 & 2 counter
12
4282
Data slave output path 3 & 4 counter
13
4283
Data slave output path 5 & 6 counter
14
4284
Data slave output path 7 & 8 counter
15
4285
Global Out Update Status
16
4286
Global Out Update Counter
17
4287
Data transfer read counter