beautypg.com

ProSoft Technology MVI56E-LDM User Manual

Page 3

background image

B Warning - Explosion Hazard - When in Hazardous Locations, turn off power before replacing or rewiring

modules.
Warning - Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is
known to be nonhazardous.

C Suitable for use in Class I, Division 2 Groups A, B, C and D Hazardous Locations or Non-Hazardous Locations.

ATEX Warnings and Conditions of Safe Usage:

Power, Input, and Output (I/O) wiring must be in accordance with the authority having jurisdiction
A Warning - Explosion Hazard - When in hazardous locations, turn off power before replacing or wiring modules.
B *Warning - Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is

known to be non-hazardous.

C These products are intended to be mounted in an IP54 enclosure. The devices shall provide external means to

prevent the rated voltage being exceeded by transient disturbances of more than 40%. This device must be used
only with ATEX certified backplanes.

D DO NOT OPEN WHEN ENERGIZED.

CPU, Memory, and OS Specifications

CPU: 400MHz ARM9 G20

Operating System: Linux (kern

el 2.6.33.7)

Linux Distribution: Debian GNU/Linux

System Memory: 64MB SDRAM

Flash Memory: 64MB ROM

Compact Flash: 64MB card provided (16GB max supported)

General Specifications

Backplane Current Load: 800 mA @ 5 V DC; 3mA @ 24V DC

Operating Temperature: 0 to 60°C (32 to 140°F)

Storage Temperature: -40 to 85°C (-40 to 185°F)

Shock: 30g Operational; 50g non-operational; Vibration: 5 g from 10 to 150 Hz

Relative Humidity: 5% to 95% (non-condensing)

LED Indicators: ERR - Application driven, APP - Application driven, OK - Application driven

4-Character, Scrolling, Alpha-numeric LED Display: Application driven - possible uses
are: Module Version, IP, Application Port Setting, Status/Error Information

All phase conductor sizes must be at least 1.3 mm(squared) and all earth ground
conductors must be at least 4mm(squared).

Ethernet Ports

2 Ethernet Ports

10/100 Mbps

RJ45 Connector,

Link and Activity Indicators

Auto-sensing crossover cable detection

Serial Ports

Full hardware handshaking control provides radio, modem, and multi-drop support.

RJ45 (DB-9M with supplied adapter cable)

Configurable RS-232 hardware handshaking

500V Optical isolation from backplane

RS-232, RS-422, RS-485 jumper-select, each port

Rx (Receive) and Tx (Transmit) LEDs, each port