beautypg.com

Part number, Module features – ProSoft Technology CLX-PVX User Manual

Page 8

background image

Page

2 QTS-

CLX-PVX

September 2009

does not support Control I/O card redundancy

The QTS-CLX-PVX communicates with the ControlLogix processor using scheduled
connections. You configure the module as a Generic Module in RSLogix 5000 with:

250 16-bit words of scheduled input data

248 16-bit words of scheduled output data

250 16-bit words of status input data

The Windows configuration program supplied with the module maps Control I/O bus
data to the scheduled data. It also:

uploads and downloads configuration data

downloads firmware to the module

saves and opens configuration files

exports aliases for use in your RSLogix 5000 application

Firmware Update

The module firmware can be updated using the Windows utility supplied (see page 32).

Part Number

The part number of the module is QTS-CLX-PVX

Module Features

The following figure shows the features of the module.

The module has:

A label that identifies the module, text QTS

Universal Comm

A 4-character scrolling display

3 LEDs, labelled NET, CLX, and OK, to indicate

the status of the I/O bus, the state of the connection
to the ControlLogix processor, and the internal state
of the module

2 BNC connectors to connect to the primary and

secondary I/O bus cables

The module supports insertion and removal under power.