QTS-CLX-PVX Page

19

addresses for data.

Failure to do so will result in writing incorrect data and may result in
injury or death.

If the QTS-CLX-PVX is in master mode and data mappings change,
make sure you clear the output data table for the module in the
ControlLogix processor before you connect the QTS-CLX-PVX to the
Control I/O bus.

What gets mapped

Master Mode

PROVOX inputs (AI, DI) are mapped to ControlLogix inputs (path:I).

PROVOX outputs (AO, DO) are mapped to ControlLogix outputs (path:O)

Diagnostics are mapped to ControlLogix inputs and status inputs (path:S).

Monitor Mode

PROVOX inputs (AI, DI) are mapped to ControlLogix inputs (path:I).

PROVOX outputs (AO, DO) are mapped to ControlLogix status inputs (path:S).

Diagnostics are mapped to ControlLogix inputs and status inputs.

Uploading and Downloading Configurations

To download a configuration to the QTS-CLX-PVX, select Actions/Download
Configuration
or use the Download Configuration to Module button on the toolbar.

To upload a configuration from the QTS-CLX-PVX, select Actions/Upload
Configuration
or use the Upload Configuration from Module button on the toolbar. The
uploaded configuration will be given the default file name Untitled.

If the RSLinx path to the module has not been set when you upload or download, an
RSLinx Path Selection window opens.