Cabling and Termination
WARNING!
Connecting the module disrupts bus traffic!
Connect the module at a time when it is safe to do so.
Connect the QTS-CLX-PVX like any other device on the Control I/O bus.
The bus cable is 75-ohm RG-6, for example Belden 9290
Terminate both ends of the primary and secondary I/O bus using 75 ohm resistors
attached to the physical ends of the bus. There should be two and only two terminators on
each bus.
Refer to the following Emerson documents for details on cabling:
section 3.8 of "Installing and Maintaining the SRx Controller Family",
PN8.0:CL6640
Installing Control I/O Subsystem (PN2.1:CP6701)
Signal Wiring and Highway System Guidelines PN1:004
Software Installation
You must uninstall any previous version of the software before you can install a new
version. Use the Windows Control Panel Add and Remove Programs to remove the old
version.
Insert the CD supplied and run the program QtsPvx.msi on the CD to install the Windows
software.