Ladder Logic

MVI69-GSC ♦ CompactLogix or MicroLogix Platform

User Manual

Generic ASCII Serial Communication Module

Page 50 of 102

ProSoft Technology, Inc.

September 24, 2010

Click OK to continue.

4 Select the Request Packet Interval value for scanning the I/O on the module.

This value represents the minimum frequency the module will handle

scheduled events. This value should not be set to less than 1 millisecond.

Values between 1 and 10 milliseconds should work with most applications.

5 Save the module. Click OK to dismiss the dialog box. The Controller

Organization window now displays the module's presence. The following

illustration shows the Controller Organization window:

6 Copy the Controller Tags from the sample program.
7 Copy the User Defined Data Types from the sample program.
8 Copy the Ladder Rungs from the sample program.
9 Save and Download (page 32) the new application to the controller and place

the processor in run mode.