beautypg.com

ProSoft Technology MVI69-GSC User Manual

Page 49

background image

MVI69-GSC ♦ CompactLogix or MicroLogix Platform

Ladder Logic

Generic ASCII Serial Communication Module

User Manual

ProSoft Technology, Inc.

Page 49 of 102

September 24, 2010

This action opens the following dialog box:

2 Select the 1769-Module (Generic 1769 Module) from the list and click OK.

3 Enter the Name, Description and Slot options for your application, using the

values in the illustration above. You must select the Comm Format as Data -
INT
in the dialog box, otherwise the module will not communicate over the
backplane of the CompactLogix rack.