Technical Data

(valid for 23 °C ± 5 °C, for less than 70 % relative humidity).

Voltage measurement: ....3 input channels with common reference point “N”

Measurement range: ....0 to 600 Vrms
Display range: ..............0 to 999.9 Vrms
Resolution: ..................0.1V
Accuracy: ....................± (1% rdg + 10D) for voltage > 80 V
Mains frequency: ........50 Hz
Input impedance: ........2 MOhm
Overload protection: ....1000 Vrms

Current measurement

Measurement range:
Input I1, I2, I3 ..........3 A to 999.9 A
Input I4 ....................3 A to 250 A
Display range: ..............0 A to 999.9 A
Resolution: ..................0.1 A
Accuracy: ....................± (2.5 % rdg +15 D)
Reduction ratio of current clamp: 0.35 mV/A
Clamp opening: ............40 mm
Admissible overload: ....10 % (for sinusoidal wave form); max. 30 seconds

Active power P

Display of active power of individual input or total value, as desired
Display range: ..............0 to 999.9 kW
A negative active power can be recognised by the sign “- “.
Resolution : ..................0.1 kW
Accuracy (for PF ≥ 0,5): ± (3.5 % rdg + 20 D)

Accuracy (for PF < 0,5): ± (4.5 % rdg + 40 D)

Apparent power S (calculation from the rms values of voltage and current)

Display of apparent power of an individual input or the total value, as desired
Display range: ..............0 – 999.9 kVA
Resolution: ..................0.1 kVA

Type of connection 1P2W

Accuracy (for PF ≥ 0,5): ± (3.5 % rdg + 20 D)

Accuracy (for PF < 0,5): ± (4.5 % rdg + 40 D)

Type of connection 1P3W, 3P3W, 3P4W

Accuracy (for PF ≥ 0,5): ± (3.5 % rdg + 20 D)

Accuracy (for PF < 0,5): ± (7.5 % rdg + 40 D)

Idle power Q (calculation out of active and apparent power)

Display of idle power of an individual input or the total value, as desired
Display range: ..............0 to 999.9 kVAr
A negative sign “- “shows a leading current.
Resolution: ..................0.1 kVAr

Formula:

Power factor PF (cos (f) (calculation out of active and apparent power)

Display of power factor of an individual input or the total value, as desired
Measurement range: .... 0 ...+1
A negative sign “- “shows a leading current.
Resolution: ..................0.001
Accuracy: ....................± (1 % rdg + 25 D)

Q =

S

P

2

2

40