All installations and services must be performed by qualified service personnel.

44

Control System Action

Main Burner

Operation

Mode of Operation

Call for Heat

Satisfied

End of Cycle

System Lockout

Repeated Trials

for Ignition.

After delay-to-fan-on period

ends, circulating air fan is

energized at heating speed.

The (optional) electronic air

cleaner and humidifier are

energized.

After the delay-to-fan-off

period ends, the circulating

air fan and {optional)

electronic air cleaner are

de-energized.

If ignition attempt is unsuccessful,

one more retry will be made before

the ignition control module goes into

system lockout.

If flame is detected,then lost,

the ignition control module will

repeat the initial ignition sequence

for a total of four recycles. After

four unsuccessful recycle attempts,

the control will go into system lockout.

The ignition control module will reset

automatically in 60 minutes.

If system is in lockout, try to

reset by interrupting the power

to the furnace at the disconnecting

switch or interrupting the call for heat

at the thermostat. If this does

not restart the system, refer to

the troubleshooting section of

this manual.

When thermostat is satisfied,

contacts open and the gas

valve is de-energized. After
proof of flame loss, inducer

and (optional) humidifier are

de-energized. The

delay-to-fan-off period begins

(180 seconds)