All installations and services must be performed by qualified service personnel.

11

Table 2: Minimum Filter Area Required (Sq. in.)

Furnace Model

Filter Type

Maximum

Rate of

Velocity

(FPM)

MHA1-50
MDA1-50

MHA1-75
MDA1-75

MHA1-100
MDA1-100

MHA1-125
MDA1-125

*THERMO
PRODUCTS
SUPPLIED
PERMANENT
FILTER

600

172

254

328

402

STANDARD
PERMANENT
FILTER

500

208

304

394

484

DISPOSABLE
TYPE
FILTER

300

344

506

656

804

* The Thermo Products supplied filter can be cut to size to fit other filter retention
systems as long as the minimum size requirement is met.

NOTICE: The filter areas in Table 2 are the minimum areas required based on
the flowrate generated by the furnace for standard heating speeds only. The
following formula can be used to determine the minimum filter area required for
cooling, if the unit is equipped with cooling. This value should then be compared
to the value shown in table 2 and the larger of the two should then be used for
determining the minimum filter area required for that installation.

FORMULA:
(tons of cooling)(400 CFM per ton)(144 sq. in. per foot) = filter area sq. inches
(max. air velocity of filter from table 5 for the filter type)

EXAMPLE: If you had an MHA1/MDA1-100 furnace and 4 tons of cooling and a
standard reusable filter.

4 tons x 400 CFM x 144 = 460 square inches for cooling
500

For heating an MHA/MDA-100 needs 328 square inches of standard reusable
filter. The filter system must be designed for the larger flow requirement
determined for cooling of 460 square inches. A filter would have to be sized so
that the area (length x width) was at least 460 sq. in.